The scope exclusion belongs at the top of this one, because it is the assumption people make. We are not an FDAI inspection service and we do not issue the annual certificate. We find what is wrong with a rated opening, tell you plainly what it is, and put it right. The certificate is a separate engagement with a separate qualification and it should come from somebody who holds one.
Clearances at head, jambs and meeting edges
NFPA 80 caps these at 1/8 in, with steel doors carrying a plus or minus 1/16 in tolerance. Measured at all three, because one compliant jamb does not carry the opening. This is the most commonly written-up finding in the whole subject and it is checkable with a tape.
Undercut
3/4 in maximum to the finished floor, dropping to 3/8 in where the bottom of the door sits more than 38 in above the floor. New flooring laid under an existing rated door is the usual cause, and it is also why the gap sometimes gets smaller than it should be rather than bigger.
Positive latching from any position
The door has to close and latch from wherever it is let go. Checked from a dead stop, not by pushing it. If it will not, the answer is the closer sizing, the arm configuration, the alignment or the strike — in that order.
Defeated hold-opens
Wedges, hooks, extinguishers and bins. If staff are propping a rated door open there is a reason the door is unusable and the reason is nearly always fixable. Listed hold-open devices released by the fire alarm are the permitted answer.
Damaged, painted-over and missing labels
A label buried under six coats of paint is a finding. A missing label means nobody can demonstrate the rating, which in a rated wall is functionally the same problem as not having one.
Unapproved field modifications
Holes cut for a new lock, a vision panel added, a kick plate over the permitted height, a bottom cut past the undercut limit. Each one is a question about what the listing permits and some of them cannot be undone.
Rated hardware on rated openings
Fire exit hardware is not the same product as panic hardware — it has no mechanical dogging, because a dogged device on a rated opening is a defeated opening. This gets swapped in error more often than you would expect.
Coordinators and astragals on pairs
A pair has to close in the right order for the meeting edges to seal and latch. A failed coordinator produces a pair where the inactive leaf closes second and the whole assembly stops working, and it presents as 'one of the doors will not shut'.