Door and frame assemblies

Fire-Rated Door Assemblies in Charlotte, NC

Repair and correction of labelled fire door assemblies in Charlotte — clearances at head, jambs, meeting edges and undercut, positive latching, defeated hold-opens, and rated hardware. We put rated openings right. We do not issue the annual inspection certificate. Call (333) 333-3333.

At a glance

Fire-Rated Door Assemblies at a glance

Assembly
Any labelled leaf and frame — hollow metal or wood — where the rating is carried by the construction and demonstrated by the label.
Governing standard
NFPA 80 for installation, clearances and maintenance. IBC Section 1010.1.3 for egress opening forces.
Fails first
The clearances and the latching, long before the leaf. A rated door that does not latch has already failed.
Not in scope
Fire door inspection certification and written FDAI reports. We correct; we do not certify.

Compare this against the other three leaf assemblies or read the standards reference.

Door and frame assemblies

A fire door that does not latch is not a fire door

Nearly everything that goes wrong with a rated opening is one of two things: a gap that is too big, or a door that does not positively latch. Both are measurable in under a minute and both are routinely made worse by somebody trying to help.

The help usually looks like this. Staff complain that a stair door is heavy. Somebody with a screwdriver backs the closer off. The door now feels fine and no longer latches from a dead stop, which means in a fire it will be pushed open by pressure and the assembly is defeated. The ADA 2010 Standards specifically exempt fire doors from the 5 lbf interior opening force limit and defer instead to the authority having jurisdiction, and this is exactly why — a closer weak enough to feel light may not close and latch the door. Meanwhile IBC Section 1010.1.3 still wants the latch to release at no more than 15 lbf, the door to set in motion at no more than 30 lbf and to swing full open at no more than 15 lbf. Those numbers are about opening it, not about whether it shuts.

If a rated door is genuinely too heavy, the fix is almost always alignment, a correctly sized closer, or an arm in the right mounting configuration. It is not less spring.

Detail

What we correct on a rated opening

The scope exclusion belongs at the top of this one, because it is the assumption people make. We are not an FDAI inspection service and we do not issue the annual certificate. We find what is wrong with a rated opening, tell you plainly what it is, and put it right. The certificate is a separate engagement with a separate qualification and it should come from somebody who holds one.

Clearances at head, jambs and meeting edges

NFPA 80 caps these at 1/8 in, with steel doors carrying a plus or minus 1/16 in tolerance. Measured at all three, because one compliant jamb does not carry the opening. This is the most commonly written-up finding in the whole subject and it is checkable with a tape.

Undercut

3/4 in maximum to the finished floor, dropping to 3/8 in where the bottom of the door sits more than 38 in above the floor. New flooring laid under an existing rated door is the usual cause, and it is also why the gap sometimes gets smaller than it should be rather than bigger.

Positive latching from any position

The door has to close and latch from wherever it is let go. Checked from a dead stop, not by pushing it. If it will not, the answer is the closer sizing, the arm configuration, the alignment or the strike — in that order.

Defeated hold-opens

Wedges, hooks, extinguishers and bins. If staff are propping a rated door open there is a reason the door is unusable and the reason is nearly always fixable. Listed hold-open devices released by the fire alarm are the permitted answer.

Damaged, painted-over and missing labels

A label buried under six coats of paint is a finding. A missing label means nobody can demonstrate the rating, which in a rated wall is functionally the same problem as not having one.

Unapproved field modifications

Holes cut for a new lock, a vision panel added, a kick plate over the permitted height, a bottom cut past the undercut limit. Each one is a question about what the listing permits and some of them cannot be undone.

Rated hardware on rated openings

Fire exit hardware is not the same product as panic hardware — it has no mechanical dogging, because a dogged device on a rated opening is a defeated opening. This gets swapped in error more often than you would expect.

Coordinators and astragals on pairs

A pair has to close in the right order for the meeting edges to seal and latch. A failed coordinator produces a pair where the inactive leaf closes second and the whole assembly stops working, and it presents as 'one of the doors will not shut'.

The four measurements, in the order we take them

Head first, because it is the one that moves when a frame spreads. Then both jambs, separately — a compliant hinge jamb tells you nothing about the strike jamb. Then the meeting edges if it is a pair. Then the undercut, measured to the finished floor rather than the slab, because the finished floor is what the code cares about and it is what changed when somebody laid new vinyl.

  • Head — 1/8 in maximum, steel tolerance plus or minus 1/16 in
  • Hinge jamb — 1/8 in maximum
  • Strike jamb — 1/8 in maximum
  • Meeting edges on a pair — 1/8 in maximum
  • Undercut — 3/4 in maximum, or 3/8 in where the bottom rail is over 38 in above the finished floor

What changes the scope on a rated opening

What changes the scope on a rated opening
FindingWhat it turns into
Clearance out at the head or a jambFrame adjustment, or in some cases a different leaf. Not something that is packed out.
Undercut too large after new flooringA bottom repair within what the listing permits, or a new leaf if it is past it.
Door will not latchCloser sizing, arm configuration, alignment or strike work. Usually one of the first two.
Missing or illegible labelA conversation about what can be demonstrated, and it may not have an on-site answer.

No figures appear in that table and none appear anywhere on this site, because a price quoted before anybody has seen the opening is a number somebody ends up unhappy about. Those are the variables that decide it.

Why us

How we handle this one

We will not turn the closer down

It is the most requested fix on a rated opening and it is the one that defeats it. We will explain why at the door with the latch face in front of you.

Measured, not eyeballed

Head, both jambs, meeting edges, undercut. Four numbers against published limits, written down.

We read the label before anything is cut

Field modifications on a labelled assembly are governed by what the listing permits and some of them are irreversible.

Fire exit hardware is not panic hardware

No dogging on a rated opening. We check what is actually fitted rather than what the schedule says.

No certificate, stated up front

You will never be surprised at the end of a visit by finding out we cannot sign something.

Process

How the job runs

Step 1. Photograph both labels before the visit if you can

Hinge edge of the leaf, frame rabbet. It shortens everything.

Step 2. Four measurements

Head, jambs, meeting edges, undercut.

Step 3. Latch test from a dead stop

Released from 90 degrees, hands off, no push.

Step 4. Identify the real cause of any weight complaint

Alignment, sizing or arm configuration. Then fix that.

Step 5. Correct it, then take the same four measurements again

Before and after, both written down. A correction nobody re-measured is a correction nobody can show an inspector.

Other services in Charlotte

Aluminum Storefront Entry Systems

Extruded aluminum entrances — the doors the public touches, and the ones that rack at the corners before they fail anywhere else.

Aluminum Storefront Entry Systems

Hollow Metal Openings and Frames

Steel leaves and frames — where the wall gives up before the door does, and corrosion starts at the toe of the frame.

Hollow Metal Openings and Frames

Wood and Flush Door Repair

Architectural wood and flush leaves — moisture at the bottom rail, then hinge screws, then edge banding. In that order, nearly always.

Wood and Flush Door Repair

Panic Hardware and Egress Devices

Push bars and exit devices — rim, mortise, surface vertical rod and concealed vertical rod, and the difference between panic and fire exit hardware.

Panic Hardware and Egress Devices

Door Closers and Operating Force

Closers, arms, sweep and latch speed, and the published opening force limits that decide whether an opening complies.

Door Closers and Operating Force

Commercial Locks, Cylinders and Keying

Mortise and bored locksets, cylinders and keying schedules — and the egress rule that decides what is allowed on the opening.

Commercial Locks, Cylinders and Keying

Call (333) 333-3333

Photograph the label on the hinge edge before you call. It answers half the questions.

Call (333) 333-3333

Charlotte commercial doors(333) 333-3333 Call now